The casing is usually used in the basement of the building, and it is an iron ring used to protect the pipeline or to facilitate the installation of the pipeline. The classification of casing includes rigid casing, flexible waterproof casing, steel pipe casing and iron casing.
Bushing is an insulating device that leads live conductors into electrical equipment or through walls. The former is called electrical bushing and the latter is called wall bushing. The casing structure is generally composed of three parts: conductor (guide rod), insulator and metal flange. The conductors pass along the axis of the cylindrical insulator, and the metal annular flange is installed outside the insulator and used for grounding. The bushing is an insulating structure with a strong vertical electric field component. The electric field strength at the metal flange is very large, and it is easy to generate corona discharge and glide discharge along the surface of the medium. The radial electric field strength between the flange and the guide rod is also very high, and the breakdown of the insulating medium is prone to occur. In addition to the use of a single solid insulating material for bushings of 35kV and below, multiple insulating materials are often used or electric field uniformity measures are adopted to make the axial and tangential electric field distributions tend to be uniform.
The design of the casing is usually to meet:
① No partial discharge or thermal breakdown occurs under long-term working voltage;
② No glide flash discharge occurs during the power frequency withstand voltage test;
③ No breakdown or flashover occurs during power frequency and impulse voltage tests.